 Operation Fundamentals

The Multi-air-gap SPD Module includes 9 air-gaps connected in serial (G1 to G9, Fig.2). Each air-gap consists of one pair of carbon-electrode separated by an insulation ring, and each air-gap but for G1 is paralleled by a capacitor (C1 to C8). Based on such a design, the SPD is non-conductive on the maximum continuous operation voltage Uc, in case of subjected lightning surge over-voltages, the gap G1 breakdowns at first due to nearly all surge voltages applying on it, because G2 to G9 are short-circuited by the capacitors. After G1 has been turned into conduction, G2 exposed to surge voltages and breakdown immediately, and then G3 to G9. It is obvious that the holdover voltage of the HIT-G50 is the sum of the holdover voltage of 9 gaps that is far more than the Uc, and therefore ,the SPD will turn off immediately after the surge voltages ended, hence no follow-current occurs.          

 Features

 * Suitable for Class I Test SPDs;

 * High surge current rating up to 50 kA, 10/350 wave;

 * No leakage current and no follow-current;

Designation

HIT-G && / xxx

HIT ­---- Brand

&& ---- Iimp value (10/350)

xxx ---- Max. continuous operating voltage  Uc

Technical Date

Technical Data

Type

HIT G15/xxx

150

255

350

440

In accordance with

IEC61643-1:2005

Category IEC/VDE

I/ B

Max. continuous operating voltage Uc

150

255

350

440

Max. discharge current(8/20) Imax

100KA

Lightning impulse current (10/350) Iimp

15KA

Voltage protection level at 1kV/μS

2.5KV

2.5KV

2.5KV

2.5KV

Response time

100 ns

Leakage current

No

Follow current

No

Insulation resistance

103 MΩ

Operating temperature range

- 40ºC … + 80ºC

Cross-section of connection wire

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Installation width

2 modules, DIN 43880

Enclosure material

thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

Technical Data

Type

HIT G25/xxx

150

255

350

440

In accordance with

IEC61643-1

Category IEC/VDE

I/ B

Max. continuous operating voltage Uc

150

255

350

440

Max. discharge current(8/20) Imax

120KA

Lightning impulse current (10/350) Iimp

25KA

Voltage protection level at 1kV/μS

2.5KV

2.5KV

2.5KV

2.5KV

Response time

100 ns

Leakage current

No

Follow current

No

Insulation resistance

103 MΩ

Operating temperature range

- 40ºC … + 80ºC

Cross-section of connection wire

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Installation width

2 modules, DIN43880

Enclosure material

thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

Technical Data

Type

HIT G50/xxx

150

255

350

440

In accordance with

IEC61643-1

Category IEC/VDE

I/ B

Max. continuous operating voltage Uc

150

255

350

440

Max. discharge current(8/20) Imax

140KA

Lightning impulse current (10/350) Iimp

50KA

Voltage protection level at 1kV/μS

2.5KV

2.5KV

2.5KV

2.5KV

Response time

100 ns

Leakage current

No

Follow current

No

Insulation resistance

103 MΩ

Operating temperature range

- 40ºC … + 80ºC

Cross-section of connection wire

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Installation width

2 modules, DIN43880

Enclosure material

thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

[Print Current Page] [Return]
  • 14/F, Cambridge House, 26-28 Cameron Road, Tsimshatsui, Kowloon, Hong Kong
  • Tel:+852-82263670; Guangzhou Office: +86-20-84214297
  • Fax:+852-82263671; Guangzhou Office:+86-20-84214192
  • E-mail.: sales@hk-hitech.com; sales@prosurgeelectronics.com
  • Hitech (HK) Co., Ltd.
For any questions or bottleneck problems need to get help from our engineers, please send e-mail to support@hk-hitech.com , our experts will give you best solution, you will get feedback within 24 hours.
页面点击数: