Three-phase AC Protector (SPD) Specification sheets

60KA Per Mode

System voltage(50/60Hz)

208V/120

400/230

480/277

240/120X208

240

480

600

Phase Configuration

Three-phase WYE

Three-phase WYE

Three-phase TT/TN

Three-phase

IT

Three-phase WYE

3-phase GHL DELTA

3-phase DELTA

3-phase DELTA

3-phase DELTA

Model No.

B60/10M-175

B60/4M-175

B60/10M-320

B60/4M-320

B60/3M-385

B60/10M-350

B60/4M-

350

B60/10M-

175/320

B60/4M-

175/320

B60/3M-320

B60/3M-640

B60/3M-780

Mode Protected

L-N, L-G,

L-L, N-G

L-N, N-G

L-N, L-G, L-L,  N-G

L-N, N-G

L-G

L-N, L-G,

L-L, N-G

L-N, N-G

L-N, L-G,

L-L, N-G

L-N, N-G

L-L,L-G

L-L

L-L

Max. Discharge Current Imax (8/20)

60KA

60KA

60KA

60KA

60KA

60KA

60KA

60KA

60KA

60KA

60KA

60KA

Nominal Discharge Current  In (8/20)

30KA

30KA

30KA

30KA

30KA

30KA

30KA

30KA

30KA

30KA

30KA

30KA

Let through voltage @ 20KA

L - N

750V

750V

1250V

1250V

N/A

1300V

1300V

750V/1250V

750V/1250V

N/A

N/A

N/A

L - G

750V

N/A

1250V

N/A

1700V

1300V

N/A

750V/1250V

N/A

1250V

N/A

N/A

N - G

750V

750V

1250V

1250V

N/A

1300V

1300V

750V

750V

N/A

N/A

N/A

L - L

1500V

N/A

2500V

N/A

N/A

2600V

N/A

1250V/2500V

N/A

1250V

2400V

3000V

Let through Voltage

@ 6KV/3KA

L - N

500V

500V

950V

950V

N/A

1100V

1100V

500V/950V

500V/950V

N/A

N/A

N/A

L - G

500V

N/A

950V

N/A

1200V

1100V

N/A

500V/950V

N/A

950V

N/A

N/A

N - G

500V

500V

950V

950V

N/A

1100V

1100V

500V

500V

N/A

N/A

N/A

L - L

1000V

N/A

1900V

N/A

N/A

2200V

N/A

950V/1900V

950V/1900V

950V

1800V

2300V

Let through Voltage

@ 20KV/10KA

L - N

800V

800V

1350V

1350V

N/A

1500V

1500V

800/1350V

800/1350V

N/A

N/A

N/A

L - G

800V

N/A

1350V

N/A

1700V

1500V

N/A

800/1350V

N/A

1350V

N/A

N/A

N - G

800V

800V

1350V

1350V

N/A

1500V

1500V

800V

800V

N/A

N/A

N/A

L - L

1600V

N/A

1700V

N/A

N/A

3000V

N/A

1350V/2700V

N/A

1350V

2400V

2900V

Clamping voltage

@ In

L - N

800V

800V

1400V

1400V

N/A

1500V

1500V

800V/1400V

800V/1400V

N/A

N/A

N/A

L - G

800V

N/A

1400V

N/A

1700V

1500V

N/A

800V/1400V

N/A

1400V

N/A

N/A

N - G

800V

800V

1400V

1400V

N/A

1500V

1500V

800V

800V

N/A

N/A

N/A

L - L

1600V

N/A

2800V

N/A

N/A

3000V

N/A

1400V/2800V

N/A

1400V

2500V

3000V

Sensitivity of Surge counter

≒3kA(8/20米s)

Connecting cable section area

16mm2-35mm2

Working environments

Temperature 每40⊥‵+70⊥, Humidity relative 5~95% (25⊥) , Altitude≒3km

Special Specification is available according to customers requirements; maybe GDT is better for N 每 PE in some application

80KA Per Mode

System voltage(50/60Hz)

208V/120

400/230

480/277

240/120X208

240

480

600

Phase Configuration

Three-phase WYE

Three-phase WYE

Three-phase TT/TN

Three-phase

IT

Three-phase WYE

3-phase GHL DELTA

3-phase DELTA

3-phase DELTA

3-phase DELTA

Model No.

B80/10M-175

B80/4M-175

B80/10M-320

B80/4M-320

B80/3M-385

B80/10M-350

B80/4M-

350

B80/10M-

175/320

B80/4M-

175/320

B80/3M-320

B80/3M-640

B80/3M-780

Mode Protected

L-N, L-G,

L-L, N-G

L-N, N-G

L-N, L-G, L-L,  N-G

L-N, N-G

L-G

L-N, L-G,

L-L, N-G

L-N, N-G

L-N, L-G,

L-L, N-G

L-N, N-G

L-L,L-G

L-L

L-L

Max. Discharge Current

Imax (8/20)

80KA

80KA

80KA

80KA

80KA

80KA

80KA

80KA

80KA

80KA

80KA

80KA

Nominal Discharge Current  In (8/20)

40KA

40KA

40KA

40KA

40KA

40KA

40KA

40KA

40KA

40KA

40KA

40KA

Let through voltage @ 20KA

L - N

750V

750V

1250V

1250V

N/A

1300V

1300V

750V/1250V

750V/1250V

N/A

N/A

N/A

L - G

750V

N/A

1250V

N/A

1700V

1300V

N/A

750V/1250V

N/A

1250V

N/A

N/A

N - G

750V

750V

1250V

1250V

N/A

1300V

1300V

750V

750V

N/A

N/A

N/A

L - L

1500V

N/A

2500V

N/A

N/A

2600V

N/A

1250V/2500V

N/A

1250V

2400V

3000V

Let through Voltage

@ 6KV/3KA

L - N

500V

500V

950V

950V

N/A

1100V

1100V

500V/950V

500V/950V

N/A

N/A

N/A

L - G

500V

N/A

950V

N/A

1200V

1100V

N/A

500V/950V

N/A

950V

N/A

N/A

N - G

500V

500V

950V

950V

N/A

1100V

1100V

500V

500V

N/A

N/A

N/A

L - L

1000V

N/A

1900V

N/A

N/A

2200V

N/A

950V/1900V

950V/1900V

950V

1800V

2300V

Let through Voltage

@ 20KV/10KA

L - N

800V

800V

1350V

1350V

N/A

1500V

1500V

800/1350V

800/1350V

N/A

N/A

N/A

L - G

800V

N/A

1350V

N/A

1700V

1500V

N/A

800/1350V

N/A

1350V

N/A

N/A

N - G

800V

800V

1350V

1350V

N/A

1500V

1500V

800V

800V

N/A

N/A

N/A

L - L

1600V

N/A

1700V

N/A

N/A

3000V

N/A

1350V/2700V

N/A

1350V

2400V

2900V

Clamping voltage

@ In

L - N

800V

800V

1400V

1400V

N/A

1500V

1500V

800V/1400V

800V/1400V

N/A

N/A

N/A

L - G

800V

N/A

1400V

N/A

1700V

1500V

N/A

800V/1400V

N/A

1400V

N/A

N/A

N - G

800V

800V

1400V

1400V

N/A

1500V

1500V

800V

800V

N/A

N/A

N/A

L - L

1600V

N/A

2800V

N/A

N/A

3000V

N/A

1400V/2800V

N/A

1400V

2500V

3000V

Sensitivity of Surge counter

≒3kA(8/20米s)

Connecting cable section area

16mm2-35mm2

Working environments

Temperature 每40⊥‵+70⊥, Humidity relative 5~95% (25⊥) , Altitude≒3km

Special Specification is available according to customers requirements; maybe GDT is better for N-PE in some application

100KA Per Mode

System voltage(50/60Hz)

208V/120

400/230

480/277

240/120X208

240

480

600

Phase Configuration

Three-phase WYE

Three-phase WYE

Three-phase TT/TN

Three-phase

IT

Three-phase WYE

3-phase GHL DELTA

3-phase DELTA

3-phase DELTA

3-phase DELTA

Model No.

B100/10M-175

B100/4M-

175

B100/10M-320

B100/4M-

320

B100/3M-

385

B100/10M-350

B100/4M-

350

B100/10M-

175/320

B100/4M-

175/320

B100/3M-

320

B100/3M-640

B100/3M-780

Mode Protected

L-N, L-G,

L-L, N-G

L-N, N-G

L-N, L-G, L-L,  N-G

L-N, N-G

L-G

L-N, L-G,

L-L, N-G

L-N, N-G

L-N, L-G,

L-L, N-G

L-N, N-G

L-L,L-G

L-L

L-L

Max. Discharge Current

Imax (8/20)

100KA

100KA

100KA

100KA

100KA

100KA

100KA

100KA

100KA

100KA

100KA

100KA

Nominal Discharge Current  In (8/20)

50KA

50KA

50KA

50KA

50KA

50KA

50KA

50KA

50KA

50KA

50KA

50KA

Let through voltage @ 20KA

L - N

750V

750V

1250V

1250V

N/A

1300V

1300V

750V/1250V

750V/1250V

N/A

N/A

N/A

L - G

750V

N/A

1250V

N/A

1700V

1300V

N/A

750V/1250V

N/A

1250V

N/A

N/A

N - G

750V

750V

1250V

1250V

N/A

1300V

1300V

750V

750V

N/A

N/A

N/A

L - L

1500V

N/A

2500V

N/A

N/A

2600V

N/A

1250V/2500V

N/A

1250V

2400V

3000V

Let through Voltage

@ 6KV/3KA

L - N

500V

500V

950V

950V

N/A

1100V

1100V

500V/950V

500V/950V

N/A

N/A

N/A

L - G

500V

N/A

950V

N/A

1200V

1100V

N/A

500V/950V

N/A

950V

N/A

N/A

N - G

500V

500V

950V

950V

N/A

1100V

1100V

500V

500V

N/A

N/A

N/A

L - L

1000V

N/A

1900V

N/A

N/A

2200V

N/A

950V/1900V

950V/1900V

950V

1800V

2300V

Let through Voltage

@ 20KV/10KA

L - N

800V

800V

1350V

1350V

N/A

1500V

1500V

800/1350V

800/1350V

N/A

N/A

N/A

L - G

800V

N/A

1350V

N/A

1700V

1500V

N/A

800/1350V

N/A

1350V

N/A

N/A

N - G

800V

800V

1350V

1350V

N/A

1500V

1500V

800V

800V

N/A

N/A

N/A

L - L

1600V

N/A

1700V

N/A

N/A

3000V

N/A

1350V/2700V

N/A

1350V

2400V

2900V

Clamping voltage

@ In

L - N

800V

800V

1400V

1400V

N/A

1500V

1500V

800V/1400V

800V/1400V

N/A

N/A

N/A

L - G

800V

N/A

1400V

N/A

1700V

1500V

N/A

800V/1400V

N/A

1400V

N/A

N/A

N - G

800V

800V

1400V

1400V

N/A

1500V

1500V

800V

800V

N/A

N/A

N/A

L - L

1600V

N/A

2800V

N/A

N/A

3000V

N/A

1400V/2800V

N/A

1400V

2500V

3000V

Sensitivity of Surge counter

≒3kA(8/20米s)

Connecting cable section area

16mm2-35mm2

Working environments

Temperature 每40⊥‵+70⊥, Humidity relative 5~95% (25⊥) , Altitude≒3km

Special Specification is available according to customers requirements; maybe GDT is better for N-PE in some application

120KA Per Mode

System voltage(50/60Hz)

208V/120

400/230

480/277

240/120X208

240

480

600

Phase Configuration

Three-phase WYE

Three-phase WYE

Three-phase TT/TN

Three-phase

IT

Three-phase WYE

3-phase GHL DELTA

3-phase DELTA

3-phase DELTA

3-phase DELTA

Model No.

B120/10M-175

B120/4M-

175

B120/10M-320

B120/4M-

320

B120/3M-

385

B120/10M-350

B120/4M-

350

B120/10M-

175/320

B120/4M-

175/320

B120/3M-

320

B120/3M-640

B120/3M-780

Mode Protected

L-N, L-G,

L-L, N-G

L-N, N-G

L-N, L-G, L-L,  N-G

L-N, N-G

L-G

L-N, L-G,

L-L, N-G

L-N, N-G

L-N, L-G,

L-L, N-G

L-N, N-G

L-L,L-G

L-L

L-L

Max. Discharge Current

Imax (8/20)

120KA

120KA

120KA

120KA

120KA

120KA

120KA

120KA

120KA

120KA

120KA

120KA

Nominal Discharge Current  In (8/20)

60KA

60KA

60KA

60KA

60KA

60KA

60KA

60KA

60KA

60KA

60KA

60KA

Let through voltage @ 20KA

L - N

750V

750V

1250V

1250V

N/A

1300V

1300V

750V/1250V

750V/1250V

N/A

N/A

N/A

L - G

750V

N/A

1250V

N/A

1700V

1300V

N/A

750V/1250V

N/A

1250V

N/A

N/A

N - G

750V

750V

1250V

1250V

N/A

1300V

1300V

750V

750V

N/A

N/A

N/A

L - L

1500V

N/A

2500V

N/A

N/A

2600V

N/A

1250V/2500V

N/A

1250V

2400V

3000V

Let through Voltage

@ 6KV/3KA

L - N

500V

500V

950V

950V

N/A

1100V

1100V

500V/950V

500V/950V

N/A

N/A

N/A

L - G

500V

N/A

950V

N/A

1200V

1100V

N/A

500V/950V

N/A

950V

N/A

N/A

N - G

500V

500V

950V

950V

N/A

1100V

1100V

500V

500V

N/A

N/A

N/A

L - L

1000V

N/A

1900V

N/A

N/A

2200V

N/A

950V/1900V

950V/1900V

950V

1800V

2300V

Let through Voltage

@ 20KV/10KA

L - N

800V

800V

1350V

1350V

N/A

1500V

1500V

800/1350V

800/1350V

N/A

N/A

N/A

L - G

800V

N/A

1350V

N/A

1700V

1500V

N/A

800/1350V

N/A

1350V

N/A

N/A

N - G

800V

800V

1350V

1350V

N/A

1500V

1500V

800V

800V

N/A

N/A

N/A

L - L

1600V

N/A

1700V

N/A

N/A

3000V

N/A

1350V/2700V

N/A

1350V

2400V

2900V

Clamping voltage

@ In

L - N

800V

800V

1400V

1400V

N/A

1500V

1500V

800V/1400V

800V/1400V

N/A

N/A

N/A

L - G

800V

N/A

1400V

N/A

1700V

1500V

N/A

800V/1400V

N/A

1400V

N/A

N/A

N - G

800V

800V

1400V

1400V

N/A

1500V

1500V

800V

800V

N/A

N/A

N/A

L - L

1600V

N/A

2800V

N/A

N/A

3000V

N/A

1400V/2800V

N/A

1400V

2500V

3000V

Sensitivity of Surge counter

≒3kA(8/20米s)

Connecting cable section area

16mm2-35mm2

Working environments

Temperature 每40⊥‵+70⊥, Humidity relative 5~95% (25⊥) , Altitude≒3km

Special Specification is available according to customers requirements; maybe GDT is better for N-PE in some application

150KA Per Mode

System voltage(50/60Hz)

208V/120V

400V/230V

480V/277V

240V

480V

Phase Configuration

Three-phase WYE

Three-phase WYE

Three-phase TT/TN

Three-phase

IT

Three-phase WYE

3-phase DELTA

3-phase DELTA

Model No.

B150-3/ 10M -175

B150-3/ 4M -175

B150-3/ 10M -320

B150-3/ 4M -320

B150-3/ 3M -385

B150-3/ 10M -350

B150-3/ 4M -350

B150-3/ 3M -320

B150-3/ 3M -640

Mode Protected

L-N, L-G,

L-L, N-G

L-N, N-G

L-N, L-G,

L-L, N-G

L-N, N-G

L-G

L-N, L-G,

L-L, N-G

L-N, N-G

L-L,L-G

L-L

Max. Discharge Current Imax

150KA

150KA

150KA

150KA

150KA

150KA

150KA

150KA

150KA

Nominal Discharge Current In

70KA

70KA

70KA

70KA

70KA

70KA

70KA

70KA

70KA

Let through voltage @ 20KA

L - N

750V

750V

1250V

1250V

N/A

1300V

1300V

N/A

N/A

L - G

750V

N/A

1250V

N/A

1700V

1300V

N/A

1250V

N/A

N - G

750V

750V

1250V

1250V

N/A

1300V

1300V

N/A

N/A

L - L

1500V

N/A

2500V

N/A

N/A

2600V

N/A

1250V

2400V

Clamping voltage

@ In

L - N

800V

800V

1400V

1400V

N/A

1500V

1500V

N/A

N/A

L - G

800V

N/A

1400V

N/A

1700V

1500V

N/A

1400V

N/A

N - G

800V

800V

1400V

1400V

N/A

1500V

1500V

N/A

N/A

L - L

1600V

N/A

2800V

N/A

N/A

3000V

N/A

1400V

2500V

Sensitivity of Surge counter

≒3kA(8/20米s)

Enclosure material

Steel, IP50

Connecting cable section area

16mm2 -35mm2

Working environments

Temperature 每 40 ⊥ ‵ + 70 ⊥ , Humidity relative 5~95% ( 25 ⊥ ) , Altitude≒ 3km

Special Specification is available according to customers requirements; maybe GDT is better for N-PE in some application

200KA Per Mode

System voltage(50/60Hz)

208V/120V

400V/230V

480V/277V

240V

480V

Phase Configuration

Three-phase WYE

Three-phase WYE

Three-phase TT/TN

Three-phase

IT

Three-phase WYE

3-phase DELTA

3-phase DELTA

Model No.

B200-3/ 10M -175

B200-3/ 4M -175

B200-3/ 10M -320

B200-3/ 4M -320

B200-3/ 3M -385

B200-3/ 10M -350

B200-3/ 4M -350

B200-3/ 3M -320

B200-3/ 3M -640

Mode Protected

L-N, L-G,

L-L, N-G

L-N, N-G

L-N, L-G,

L-L, N-G

L-N, N-G

L-G

L-N, L-G,

L-L, N-G

L-N, N-G

L-L,L-G

L-L

Max. Discharge Current Imax

200KA

200KA

200KA

200KA

200KA

200KA

200KA

200KA

200KA

Nominal Discharge Current In

100KA

100KA

100KA

100KA

100KA

100KA

100KA

100KA

100KA

Let through voltage @ 20KA

L - N

750V

750V

1250V

1250V

N/A

1300V

1300V

N/A

N/A

L - G

750V

N/A

1250V

N/A

1700V

1300V

N/A

1250V

N/A

N - G

750V

750V

1250V

1250V

N/A

1300V

1300V

N/A

N/A

L - L

1500V

N/A

2500V

N/A

N/A

2600V

N/A

1250V

2400V

Clamping voltage

@ In

L - N

800V

800V

1400V

1400V

N/A

1500V

1500V

N/A

N/A

L - G

800V

N/A

1400V

N/A

1700V

1500V

N/A

1400V

N/A

N - G

800V

800V

1400V

1400V

N/A

1500V

1500V

N/A

N/A

L - L

1600V

N/A

2800V

N/A

N/A

3000V

N/A

1400V

2500V

Sensitivity of Surge counter

≒3kA(8/20米s)

Enclosure material

Steel, IP50

Connecting cable section area

16mm2 -35mm2

Working environments

Temperature 每 40 ⊥ ‵ + 70 ⊥ , Humidity relative 5~95% ( 25 ⊥ ) , Altitude≒ 3km

Special Specification is available according to customers requirements; maybe GDT is better for N-PE in some application

 

 

 

[Print Current Page] [Return]
  • 14/F, Cambridge House, 26-28 Cameron Road, Tsimshatsui, Kowloon, Hong Kong
  • Tel:+852-82263670; Guangzhou Office: +86-20-84214297
  • Fax:+852-82263671; Guangzhou Office:+86-20-84214192
  • E-mail.: sales@hk-hitech.com; sales@prosurgeelectronics.com
  • Hitech (HK) Co., Ltd.
For any questions or bottleneck problems need to get help from our engineers, please send e-mail to support@hk-hitech.com , our experts will give you best solution, you will get feedback within 24 hours.