THE PARAMETERS OF SURGE ARRESTORS
|
Type
Parameters |
HY5W-9/25.5 |
HY5W-12/34 |
HY5W-15/42.5 |
HY5W-18/51 |
HY5W-24/68 |
HY10W-15/42.5 |
HY10W-24/68 |
HY10W-30/85 |
HY10W-33/93.5 |
HY10W-36/102 |
HY10W-42/119 |
HY10W-60/170 |
|
1 |
Max. Continuous operating voltage, UMCOV, kVr.m.s. |
7.2 |
9.6 |
12 |
14.4 |
19.2 |
12 |
19.2 |
24 |
26.4 |
28.8 |
33.6 |
48 |
|
2 |
Rated voltage, UR, kVr.m.s. |
9 |
12 |
15 |
18 |
24 |
15 |
24 |
30 |
33 |
36 |
42 |
60 |
|
3 |
Rated discharge current, kA peak value |
5 |
5 |
5 |
5 |
5 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
|
4 |
Min. D.C. reference voltage, U1mA, kV |
13 |
17.2 |
21.5 |
25.8 |
34.4 |
21.5 |
34.4 |
43 |
47.3 |
51.6 |
60.2 |
86 |
|
5 |
Max. residual voltage at steep impulse 1/10¦Ìs, kV |
29.3 |
39.1 |
48.9 |
58.7 |
78.2 |
48.9 |
78.2 |
97.8 |
107.5 |
117.3 |
136.8 |
195.5 |
|
6 |
Max. residual voltage at lighting impulse 8/20¦Ìs, kV |
25.5 |
34 |
42.5 |
14.4 |
19.2 |
42.5 |
68 |
85 |
93.5 |
102 |
119 |
170 |
|
7 |
Max. residual voltage at switching impulse 30/60 ¦Ìs, kV |
/ |
/ |
/ |
/ |
/ |
36 |
57.8 |
72.2 |
79.5 |
86.7 |
101.2 |
144.5 |
|
8 |
Withstand capability at current impulse 2ms, A |
75 |
75 |
75 |
75 |
75 |
250¡«400 |
250¡«400 |
250¡«400 |
250¡«400 |
250¡«400 |
250¡«400 |
250¡«400 |
|
9 |
Withstand capability at current impulse 4/10¦Ìs, kA |
65 |
65 |
65 |
65 |
65 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
|
10 |
Housing insulation level at lighting impulse, kV |
60 |
75 |
75 |
105 |
125 |
75 |
125 |
145 |
145 |
170 |
185 |
221 |
|
11 |
Housing insulation level at power frequency in wet 1 min., kV |
23 |
30 |
30 |
40 |
50 |
30 |
50 |
60 |
60 |
70 |
80 |
110 |
|
12 |
Mechanical strength, torsional/cantilever (N.m / N) |
35/250 |
35/250 |
35/250 |
35/250 |
35/250 |
60/250 |
60/250 |
60/250 |
60/250 |
60/250 |
60/250 |
60/250 |
|
13 |
Creepage distance, mm |
227 |
291 |
351 |
419 |
540 |
355 |
545 |
675 |
675 |
740 |
875 |
1250 |
|
14 |
Dimension |
Diameter of sheds, mm |
88 |
88 |
88 |
88 |
88 |
103 |
103 |
103 |
103 |
103 |
103 |
103 |
|
Number of sheds, pcs |
3 |
4 |
5 |
6 |
8 |
5 |
8 |
10 |
10 |
11 |
13 |
18 |
|
Height of arrestors, mm |
205 |
235 |
265 |
295 |
355 |
240 |
330 |
390 |
390 |
420 |
480 |
630 |
|
Weight of arrestors, kg |
0.87 |
1.06 |
1.25 |
1.43 |
1.80 |
1.69 |
2.58 |
3.16 |
3.25 |
3.55 |
4.12 |
5.66 |
|
Type
Parameters |
HY10W-90/232 |
HY10W-72/201 |
HY10W-90/240 |
HY10W-120/325 |
HY10W-138/375 |
Y10W-120/325
Porcelain |
|
1 |
Max. Continuous operating voltage, UMCOV, kVr.m.s. |
72.5 |
57 |
70 |
96 |
111 |
96 |
|
2 |
Rated voltage, UR, kVr.m.s. |
90 |
72 |
90 |
120 |
138 |
120 |
|
3 |
Rated discharge current, kA peak value |
10 |
10 |
10 |
10 |
10 |
10 |
|
4 |
Min. D.C. reference voltage, U1mA, kV |
130 |
103 |
132 |
175 |
202 |
175 |
|
5 |
Max. residual voltage at steep impulse 1/10¦Ìs, kV |
271 |
231 |
276 |
356 |
450 |
356 |
|
6 |
Max. residual voltage at lighting impulse 8/20¦Ìs, kV |
232 |
201 |
240 |
325 |
375 |
325 |
|
7 |
Max. residual voltage at switching impulse 30/60 ¦Ìs, kV |
190 |
173 |
207 |
267 |
335 |
267 |
|
8 |
Withstand capability at current impulse 2ms, A |
600 |
600 |
600 |
600 |
600 |
600 |
|
9 |
Withstand capability at current impulse 4/10¦Ìs, kA |
100 |
100 |
100 |
100 |
100 |
100 |
|
10 |
Housing insulation level at lighting impulse, kV |
450 |
310 |
450 |
450 |
520 |
450 |
|
11 |
Housing insulation level at power frequency in wet 1 min., kV |
185 |
132 |
185 |
185 |
210 |
185 |
|
12 |
Mechanical strengthcantilever ,( N) |
1412 |
780 |
1412 |
1412 |
1412 |
3120 |
|
13 |
Creepage distance, mm |
2055 |
1860 |
3100 |
3100 |
3540 |
3200 |
|
14 |
Dimension |
Diameter of sheds, big/small, mm |
146/126 |
146/126 |
210/170 |
210/170 |
210/170 |
302/272 |
|
Number of sheds, pcs |
11/10 |
10/9 |
14/13 |
14/13 |
16/15 |
12/11 |
|
Height of arrestors, mm |
1010 |
915 |
1370 |
1370 |
1474 |
1734 |
|
Total weight, kg |
20 |
19 |
42 |
42 |
47 |
182 |
|